TIGHTSILANE™ Series Performance Test Results

The methods and results of various tests related to the coating of TIGHTSILANE™ on concrete are presented.

Basic performance test

[According to the building materials Testing Center]

Water permeability test ① (water permeability pressure 0.1kgf/cm2)

Water permeability test ① (water permeability pressure 0.1kgf/cm2)

Water permeability test ② (water permeability pressure 3.0kgf/cm2)

Water permeability test ② (water permeability pressure 3.0kgf/cm2)

water absorption test

water absorption test

penetration depth

penetration depth

Alkaline aggregate reaction suppression performance test

[By the Railway Technical Research Institute]

Test method

Specimen: Ordinary Voltland cement, 10 x 10 x 40 cm, maximum aggregate size 25 mm, total alkali content 3.0% R2O, water cement ratio 55.1% slump 11 cm, air content 4.7%
Test specimen curing conditions: After pouring, demolding after 2 days in 20℃ humid air, 300g/m2 applied to the entire surface after 14 days in 20℃ 60%RH air, outdoor exposure started after 3 days in air.
Measurement method: Periodically measure expansion rate (comparator method) and weight change

Test results

Change in expansion rate of concrete specimen (alkali content: 3.0%R2O)
Test results
Weight change of concrete specimen (alkali content: 3.0% R 2 O)
Test results

Water absorption ratio of concrete after outdoor exposure

Test method

Specimen: Ordinary boltland cement, 10×10×10cm concrete, W/C=60% slump 18cm
Cured for 14 days at 20℃ air drying
After 3 years of exposure, one side of the specimen was soaked in water, and the amount of water absorbed 24 hours later was measured to determine the weight change rate.

Test results

Test results

Accelerated weathering test

Test method

Evaluated by water absorption test after due cycle test
Base: Mortar (JIS R 5201) 70×70×20mm

Test results

Test results
Test results

Electricity transmitted through concrete after outdoor exposure

[By Kanazawa Institute of Technology]

Test method

Specimen: Ordinary boltland cement, 10×5cm concrete, W/C=60%
10 days before the specified exposure period, the specimen was taken indoors, air-dried for 10 days, then submerged in water at 20°C for 1 month, according to the rapid chloride ion permeability test according to the AASHTOT-277 standard. A low voltage of 60V was applied between a 3% NaCl aqueous solution and a 0.3% NaOH aqueous solution that were in contact with both end faces of the specimen, and the amount of electricity transmitted over 6 hours was measured.

Test results

Test results

Salt blocking property (salt penetration depth) test

Test method

1 cycle: 3% sodium chloride aqueous solution, 20℃ for 4 days,
60%RH air drying for 3 days, sodium fluorescein, silver nitrate color method
Base: Concrete (W/C: 60%) 100×100×100mm

Test results

Test results

Warm, cool, dry and wet repeated test

Test method

Conforms to JIS A6909. Track weight changes.
1 cycle: 18 hours in +20℃ water, 3 hours in -20℃ air, 3 hours in +50℃ air
Base: Mortar (JIS R 5201) 70×70×20mm

Test results

Test results